The outlet is sampled from the chamber, not from the storm tank.
After heavy rain, wait until the outlet flow has fallen to the normal band. Sample within two hours.
Do not sample while the storm tank is still spilling.
Label the bottle before you fill it, and keep the lid in a clean hand.
Rinse the bottle once with the water you are about to sample, discard that rinse, then fill.
A second bottle is only needed if the first is dropped.